Emergency setting for VRV3 standard compressor | Daikin

Аватар автора
Инструментальная мастерская
Brand : Daikin VRV3 model : RXQ12PAY13 (single CU) Emergency Operation If any of the compressor malfunctions, disable the corresponding compressor or outdoor unit, and then conduct Emergency Operation only with operational compressor or outdoor units. 1 CU system Emergency setting for standard 1 compressor. 1)Press Mode button 5 second or more (H1P)light up. 2)Press Set button 19 times 3)Press Return button once 4)Press Set button once 5)Press Return button twice 6)Press Mode button to exit Field setting can be contacted on the CU main PCB to isolate the faulty Standard 1 compressor while allowing other compressor to operate. Applicable for VRV3, VRV3Q, VRV2(410a) #VRV